Register
A register holds a measurement together with its scale and physical unit. The scale tells a reader how to convert the stored number into the displayed engineering value.
When to use it
Use it to read an energy total, voltage or another scaled measurement.
Attributes
1. Logical name
Identifies this object instance using its six-part OBIS code. Use it to distinguish this object from other instances of the same class.
2. Value
Contains the measurement value.
Read Scaler and unit (attribute 3) before interpreting an unscaled measurement.
3. Scaler and unit
Defines the decimal exponent and unit. Multiply the stored value by 10 raised to the scaler to obtain the value in that unit.
Actions
1. Reset
This action is used to reset value to default value.