I have to add a new parameter, Average RMS percentage voltage, in the instantaneous profile of the energy meter(3 Phase).
Can you suggest to me the OBIS code, although I have concluded from Blue Book, that it can be 12.7.0, but I think it should be applied if the unit is Volts, but I'm calculating this value in percentage,
So, kindly suggest, what OBIS code should be used?
Thank You, Sir ! Although it is very helpful, But I didn't find the OBIS code for the respective parameter, even I didn't found any parameters in percentage units.
Can you suggest to me the appropriate OBIS code?
Hi,
Hi,
You can use GXDLMSTranslator to find correct OBIS code.
https://www.gurux.fi/GuruxDLMSTranslator
Remove OBIS code and apply the description to filter.
OBIS code might also be defined in country-specific versions.
BR,
Mikko
Thank You, Sir ! Although it
Thank You, Sir ! Although it is very helpful, But I didn't find the OBIS code for the respective parameter, even I didn't found any parameters in percentage units.
Can you suggest to me the appropriate OBIS code?
Hi,
Hi,
It might be that there is no standard OBIS code for that. Then you need to use the manufacturer specific OBIS codes.
BR,
Mikko
Yes, Sir, Maybe, but while
Yes, Sir, Maybe, but while selecting the Manf. specific OBIS is there any restriction regarding percentage value?
Hi,
Hi,
No. It's recommended that Manufacturer-specific values are not used, but if that is not in the standard you need to use it.
BR,
Mikko
OK Sir, Thanks for your
OK Sir, Thanks for your valuable time, the information was very helpful,