<p>As per IS 15959-P2 (cluase 4 and 7.1 Table-2) PUSH doesn't required any authentication password. It has the lowest key. But when i am selecting Indian standard and association PUSH in gurux it is mandatorily asking password and hence meter is failing. Attached the screen shot both standard and tool configuration. I am using 9.0.2504.0301 version.</p>
Hi, IS 15959-P2 defines that…
Hi,
IS 15959-P2 defines that you need to use pre-established connection if you want to modify or read push messages. This is defined in "Table 2 Detailed Association Properties for the Smart Meter".
BR,
Mikko
Thanks for the reply. I am…
Thanks for the reply.
I am not reading any push messages.
I wanted to download the PUSH association. Like how we download other associations(PC,MR,US).
In Gurux tool if i select manufacturer as Indian Standard and Authentication as PUSH then it mandatorily asking password. But as per the IS PUSH doesn't need any password to download the association.
Hi, This is changed. Restart…
Hi,
This is changed. Restart GXDLMSDirector and select "New Manufacturer Settings Available" from the top menu.
GXDLMSDirector doesn't ask for the password after that.
BR,
Mikko