Hi,

I was using EMH ITZ and Moxa NPORT 5232 but it can't connect. Here my device
manufacturer emh
startprotocol: dlms
media :net
auth none
client address 10
adress type serialnumber
serial number i put 8075
logical server 0
host name 192.168.127.254
port 4059

Profile picture for user Kurumi

Kurumi

8 years 3 months ago

EMH ITZ and Moxa NPORT 5232

Hi,

First check that Moxa and meter serial port settings are same.
Then check that your settings are like described in
EMH metering GmbH settings
http://www.gurux.fi/GXDLMSDirectorExample

BR,

Mikko

iamzero5

8 years 3 months ago

In reply to EMH ITZ and Moxa NPORT 5232 by Kurumi

EMH ITZ and Moxa NPORT 5232

Hi,

Thank you for the answer and I will look at it.

I guess the problem is with the serial number I can't distinguish where is the serial number is located or should I only input the last 4 digit of the serial number.

Profile picture for user Kurumi

Kurumi

8 years 3 months ago

EMH ITZ and Moxa NPORT 5232

Hi,

Give serial number totally. A serial number is a cover on the meter.

BR,

Mikko

iamzero5

8 years 3 months ago

In reply to EMH ITZ and Moxa NPORT 5232 by Kurumi

Hi,

Hi,

Still not able to connect.
Here is the error from logs:
5:23:57 PM Initializing serial connection.
5:23:57 PM HDLC sending:/?6098075!<CR><LF>
5:24:04 PM Disconnect request
5:24:11 PM Failed to receive reply from the device in given time.
System.Exception: Failed to receive reply from the device in given time.
at GXDLMSDirector.GXDLMSDevice.InitializeConnection()
at GXDLMSDirector.MainForm.Connect(Object sender, GXAsyncWork work, Object[] parameters)

Profile picture for user Kurumi

Kurumi

8 years 3 months ago

EMH ITZ

Hi,

EMH ITZ is using IEC 62052-11. You can't use GXDLMSDirector to read your meter because your meter is not DLMS compatible.

BR,
Mikko

iamzero5

8 years 3 months ago

In reply to EMH ITZ by Kurumi

Thank you for the response.

Thank you for the response. Is there any way to read this meter?

Profile picture for user Kurumi

Kurumi

8 years 2 months ago

EMH ITZ

Hi,

You can make own app. IEC 62052-11 is ASCII based protocol, but there are some variation between meters, so it's not possible to make a generic app that can read all the meter.

BR,

Mikko

  • Create new account
  • Reset your password

Hire Us!

Latest Releases

  • Tue, 06/09/2026 - 11:16
    gurux.dlms.java 4.0.95
  • Tue, 06/09/2026 - 10:03
    Gurux.DLMS.Python 1.0.199
  • Mon, 06/08/2026 - 13:39
    gurux.dlms.cpp 9.0.2606.0801
  • Mon, 06/01/2026 - 10:15
    gurux.dlms.cpp 9.0.2606.0101
  • Thu, 05/28/2026 - 16:06
    gurux.dlms.java 4.0.94

New forum topics

  • Error reading L&G Meter
  • Pass a TCP Client to GXNet
  • Australian EDMI Mk10D (Essential Energy area)
  • Strange mix of data notificiation vs get response
  • DLMS Connection
More

Who's new

  • Tuanhgg
  • Adel
  • charnon
  • Paddles
  • Miguel Ángel
RSS feed
Privacy FAQ GXDN Issues Contact
Follow Gurux on Twitter Follow Gurux on Linkedin