By vaibhav, 30 May, 2023 Forums DLMSDirector Hello, I got some errors when I was trying to read the DLMS meter with "GXDLMSDirector". Please suggest solutions. Image Hi, Please, don't add… Hi, Please, don't add pictures. They are hard to read. One of your settings is wrong and the meter doesn't reply. What meter do you try to read (model and manufacturer) and what communication channel you are using (TCP/IP, serial)? BR, Mikko model: L&T Electrical &… Following Information on the meter model: L&T Electrical & Automation (Three Phase HTCT Multi-Port Meter) manufacturer: ER300P communication Channel: optical Prop to Serial Port USB. Please suggest. Hi, First, make sure that… Hi, First, make sure that the cable of the optical probe is downward. If I remember right the ER300P is not using Mode E, so select HDLC to interface type. Check from the meter documentation what is the used baud rate and you should be able to connect. BR, Mikko Following is the … Following is the configuration info: Name: Larsen Toubro Manufacturer: Larsen &Toubro Ltd Interface: HDLC Authentication: Low Client Address: 11 Password: Int1 Wait Time: 00:00:05 Resend Count: 3 Address Type: Default Logical Server: 0 Physical Server: 1 Media: Serial settings Serial Port: COM7 Use Maximum Baud Rate 300 Please suggest the proper solution. and let me know where to check the baud rate. Hi, You can change the baud… Hi, You can change the baud rate from the advanced button. Don't check the "Use maximum baud rate". You can try with a baud rate of 9600, but you need to check it from the meter documentation or ask the meter vendor. BR, Mikko Log in or register to post comments
Hi, Please, don't add… Hi, Please, don't add pictures. They are hard to read. One of your settings is wrong and the meter doesn't reply. What meter do you try to read (model and manufacturer) and what communication channel you are using (TCP/IP, serial)? BR, Mikko
model: L&T Electrical &… Following Information on the meter model: L&T Electrical & Automation (Three Phase HTCT Multi-Port Meter) manufacturer: ER300P communication Channel: optical Prop to Serial Port USB. Please suggest.
Hi, First, make sure that… Hi, First, make sure that the cable of the optical probe is downward. If I remember right the ER300P is not using Mode E, so select HDLC to interface type. Check from the meter documentation what is the used baud rate and you should be able to connect. BR, Mikko
Following is the … Following is the configuration info: Name: Larsen Toubro Manufacturer: Larsen &Toubro Ltd Interface: HDLC Authentication: Low Client Address: 11 Password: Int1 Wait Time: 00:00:05 Resend Count: 3 Address Type: Default Logical Server: 0 Physical Server: 1 Media: Serial settings Serial Port: COM7 Use Maximum Baud Rate 300 Please suggest the proper solution. and let me know where to check the baud rate.
Hi, You can change the baud… Hi, You can change the baud rate from the advanced button. Don't check the "Use maximum baud rate". You can try with a baud rate of 9600, but you need to check it from the meter documentation or ask the meter vendor. BR, Mikko
Hi, Please, don't add…
Hi,
Please, don't add pictures. They are hard to read.
One of your settings is wrong and the meter doesn't reply.
What meter do you try to read (model and manufacturer) and what communication channel you are using (TCP/IP, serial)?
BR,
Mikko
model: L&T Electrical &…
Following Information on the meter
model: L&T Electrical & Automation (Three Phase HTCT Multi-Port Meter)
manufacturer: ER300P
communication Channel: optical Prop to Serial Port USB.
Please suggest.
Hi, First, make sure that…
Hi,
First, make sure that the cable of the optical probe is downward.
If I remember right the ER300P is not using Mode E, so select HDLC to interface type.
Check from the meter documentation what is the used baud rate and you should be able to connect.
BR,
Mikko
Following is the …
Following is the configuration info:
Name: Larsen Toubro
Manufacturer: Larsen &Toubro Ltd
Interface: HDLC
Authentication: Low
Client Address: 11
Password: Int1
Wait Time: 00:00:05
Resend Count: 3
Address Type: Default
Logical Server: 0
Physical Server: 1
Media: Serial
settings
Serial Port: COM7
Use Maximum Baud Rate 300
Please suggest the proper solution. and let me know where to check the baud rate.
Hi, You can change the baud…
Hi,
You can change the baud rate from the advanced button. Don't check the "Use maximum baud rate".
You can try with a baud rate of 9600, but you need to check it from the meter documentation or ask the meter vendor.
BR,
Mikko