By Bhavjinder Singh , 3 July, 2018 Forums DLMSDirector Below is the trace content coming in the GXDLMSDIRECTOR: 03/07/2018 10:55:45 AM <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="93" /> <Snrm> </Snrm> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="53" /> <DisconnectRequest> </DisconnectRequest> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="93" /> <Snrm> </Snrm> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="43" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="10" /> <PDU> <AssociationRequest> <ApplicationContextName Value="LN" /> <SenderACSERequirements Value="1" /> <MechanismName Value="Low" /> <CallingAuthentication Value="4142434430303031" /> <InitiateRequest> <ProposedDlmsVersionNumber Value="06" /> <ProposedConformance> </ProposedConformance> <ProposedMaxPduSize Value="FFFF" /> </InitiateRequest> </AssociationRequest> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="2C" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="30" /> <PDU> <AssociationResponse> <ApplicationContextName Value="LN" /> <AssociationResult Value="01" /> <ResultSourceDiagnostic> <ACSEServiceUser Value="01" /> </ResultSourceDiagnostic> <ConfirmedServiceError> <Service Value="01" /> <ServiceError> <Initiate Value="IncompatibleConformance" /> </ServiceError> </ConfirmedServiceError> </AssociationResponse> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC> NOt able to connect to meter It's an indian make meter... NOt able to connect to meter I have also tried with client address: 10 but no luck.. pls help me NOt able to connect to meter Hi Mikko.. pls help me.. Im trying to connect meter with GXDLMSDIRECTOR so that i can understand better understand communication.. Meter im reading is of indian make. but im getting following error in the trace: <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="93" /> <Snrm> </Snrm> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="53" /> <DisconnectRequest> </DisconnectRequest> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="93" /> <Snrm> </Snrm> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="43" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="10" /> <PDU> <AssociationRequest> <ApplicationContextName Value="LN" /> <SenderACSERequirements Value="1" /> <MechanismName Value="Low" /> <CallingAuthentication Value="4142434430303031" /> <InitiateRequest> <ProposedDlmsVersionNumber Value="06" /> <ProposedConformance> </ProposedConformance> <ProposedMaxPduSize Value="FFFF" /> </InitiateRequest> </AssociationRequest> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="2C" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="30" /> <PDU> <AssociationResponse> <ApplicationContextName Value="LN" /> <AssociationResult Value="01" /> <ResultSourceDiagnostic> <ACSEServiceUser Value="01" /> </ResultSourceDiagnostic> <ConfirmedServiceError> <Service Value="01" /> <ServiceError> <Initiate Value="IncompatibleConformance" /> </ServiceError> </ConfirmedServiceError> </AssociationResponse> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC> Not able to connect to meter Hi, You have not selected any Conformance. You can see this selecting "Supported services" -tab from device settings. Select at least Get. BR, Mikko
NOt able to connect to meter Hi Mikko.. pls help me.. Im trying to connect meter with GXDLMSDIRECTOR so that i can understand better understand communication.. Meter im reading is of indian make. but im getting following error in the trace: <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="93" /> <Snrm> </Snrm> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="53" /> <DisconnectRequest> </DisconnectRequest> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="9" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="93" /> <Snrm> </Snrm> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="43" > <TargetAddress Value="1" /> <SourceAddress Value="20" /> <FrameType Value="10" /> <PDU> <AssociationRequest> <ApplicationContextName Value="LN" /> <SenderACSERequirements Value="1" /> <MechanismName Value="Low" /> <CallingAuthentication Value="4142434430303031" /> <InitiateRequest> <ProposedDlmsVersionNumber Value="06" /> <ProposedConformance> </ProposedConformance> <ProposedMaxPduSize Value="FFFF" /> </InitiateRequest> </AssociationRequest> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="2C" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="30" /> <PDU> <AssociationResponse> <ApplicationContextName Value="LN" /> <AssociationResult Value="01" /> <ResultSourceDiagnostic> <ACSEServiceUser Value="01" /> </ResultSourceDiagnostic> <ConfirmedServiceError> <Service Value="01" /> <ServiceError> <Initiate Value="IncompatibleConformance" /> </ServiceError> </ConfirmedServiceError> </AssociationResponse> </PDU> </HDLC> 03/07/2018 10:55:59 AM <HDLC len="1E" > <TargetAddress Value="20" /> <SourceAddress Value="1" /> <FrameType Value="73" /> <PDU> <Ua> <MaxInfoTX Value="256" /> <MaxInfoRX Value="128" /> <WindowSizeTX Value="1" /> <WindowSizeRX Value="1" /> </Ua> </PDU> </HDLC>
Not able to connect to meter Hi, You have not selected any Conformance. You can see this selecting "Supported services" -tab from device settings. Select at least Get. BR, Mikko
NOt able to connect to meter
It's an indian make meter...
NOt able to connect to meter
I have also tried with client address: 10 but no luck.. pls help me
NOt able to connect to meter
Hi Mikko.. pls help me..
Im trying to connect meter with GXDLMSDIRECTOR so that i can understand better understand communication.. Meter im reading is of indian make.
but im getting following error in the trace:
<HDLC len="9" >
<TargetAddress Value="1" />
<SourceAddress Value="20" />
<FrameType Value="93" />
<Snrm>
</Snrm>
</HDLC>
03/07/2018 10:55:59 AM
<HDLC len="9" >
<TargetAddress Value="1" />
<SourceAddress Value="20" />
<FrameType Value="53" />
<DisconnectRequest>
</DisconnectRequest>
</HDLC>
03/07/2018 10:55:59 AM
<HDLC len="1E" >
<TargetAddress Value="20" />
<SourceAddress Value="1" />
<FrameType Value="73" />
<PDU>
<Ua>
<MaxInfoTX Value="256" />
<MaxInfoRX Value="128" />
<WindowSizeTX Value="1" />
<WindowSizeRX Value="1" />
</Ua>
</PDU>
</HDLC>
03/07/2018 10:55:59 AM
<HDLC len="9" >
<TargetAddress Value="1" />
<SourceAddress Value="20" />
<FrameType Value="93" />
<Snrm>
</Snrm>
</HDLC>
03/07/2018 10:55:59 AM
<HDLC len="1E" >
<TargetAddress Value="20" />
<SourceAddress Value="1" />
<FrameType Value="73" />
<PDU>
<Ua>
<MaxInfoTX Value="256" />
<MaxInfoRX Value="128" />
<WindowSizeTX Value="1" />
<WindowSizeRX Value="1" />
</Ua>
</PDU>
</HDLC>
03/07/2018 10:55:59 AM
<HDLC len="43" >
<TargetAddress Value="1" />
<SourceAddress Value="20" />
<FrameType Value="10" />
<PDU>
<AssociationRequest>
<ApplicationContextName Value="LN" />
<SenderACSERequirements Value="1" />
<MechanismName Value="Low" />
<CallingAuthentication Value="4142434430303031" />
<InitiateRequest>
<ProposedDlmsVersionNumber Value="06" />
<ProposedConformance>
</ProposedConformance>
<ProposedMaxPduSize Value="FFFF" />
</InitiateRequest>
</AssociationRequest>
</PDU>
</HDLC>
03/07/2018 10:55:59 AM
<HDLC len="2C" >
<TargetAddress Value="20" />
<SourceAddress Value="1" />
<FrameType Value="30" />
<PDU>
<AssociationResponse>
<ApplicationContextName Value="LN" />
<AssociationResult Value="01" />
<ResultSourceDiagnostic>
<ACSEServiceUser Value="01" />
</ResultSourceDiagnostic>
<ConfirmedServiceError>
<Service Value="01" />
<ServiceError>
<Initiate Value="IncompatibleConformance" />
</ServiceError>
</ConfirmedServiceError>
</AssociationResponse>
</PDU>
</HDLC>
03/07/2018 10:55:59 AM
<HDLC len="1E" >
<TargetAddress Value="20" />
<SourceAddress Value="1" />
<FrameType Value="73" />
<PDU>
<Ua>
<MaxInfoTX Value="256" />
<MaxInfoRX Value="128" />
<WindowSizeTX Value="1" />
<WindowSizeRX Value="1" />
</Ua>
</PDU>
</HDLC>
Not able to connect to meter
Hi,
You have not selected any Conformance. You can see this selecting "Supported services" -tab from device settings.
Select at least Get.
BR,
Mikko