Hi everybody,

I am new to cosem, and I want to read information from ISKRA ME 172 using cosem protocol, but I found this protocol very difficult. I don't know from where I should start.
Could you help me?

Thanks,

Profile picture for user Kurumi

Kurumi

9 years 11 months ago

starting with ISKRA ME 172

Hi,

ISKRA ME 172 is not supporting DLMS. It supports IEC 62054-21.
IEC 62054-21 is ASCII based protocol and it's easier to use.

BR,

Mikko

Profile picture for user Bakre

Bakre

9 years 11 months ago

In reply to starting with ISKRA ME 172 by Kurumi

Hi,

Hi,
Thank you for your answer Kurumi, I want to know about ISKRA MT880, is it working with dlms or with the same protocol IEC 62054-21?
Thanks,
Best regards,

Profile picture for user Kurumi

Kurumi

9 years 10 months ago

ISKRA MT880

Hi,

ISKRA MT880 is using DLMS. You can use GXDLMSDirector to read it.
BR,

Mikko

Profile picture for user Kurumi

Kurumi

9 years 9 months ago

ISKRA ME 172

Hi,

Iskra ME 172 is not supporting DLMS. It's using IEC 62054-21 also know as IEC 1107.
IEC 62054-21 is ASCII protocol and It's easier. Problem is that there are lots of variations between different meters. If you do not need anything special you can try to get readout from the meter.
(I'm not sure is this meter supporting it, but you can try).

Set serial port baudrate to 300 and Data bits: 7, Parity: Even and StopBits: 1.
Then send /?!r\n to the port. Meter should response and send some information.
If you wait more usually Mode A is used and meter send readout.

BR,

Mikko

BR,

Mikko

Profile picture for user Bakre

Bakre

9 years 9 months ago

Can't communicate with the ISKRA ME 172

Hi,

I want to communicate with the ISKRA ME 172 via RS 485, I have written a code respecting the IEC 1107 protocol, but I haven't got any answer.

Thanks.

Profile picture for user Kurumi

Kurumi

9 years 9 months ago

starting with ISKRA ME 172

Hi,

Try to change baudrate to 4800 or 9600. Then try to change settings from 7E1 to 8N1.
Are you using optical strobe or serial port connection?

BR,

Mikko

Profile picture for user Bakre

Bakre

9 years 9 months ago

Starting with ISKRA ME 172

Hi,

Thank you Mikko for your reply, I have tried all baudrates possible in the protocol. I am using RS485.

Thanks.

h.abdali

5 years 6 months ago

Hi Bakre,

Hi Bakre,

did it work for you?

hard

5 years 3 months ago

Meet the same problem. RS-485

Meet the same problem. RS-485
Tried baudrates 300, 4800, 9600 (Representative sad this is default). Tried 8N1, 7E1.

None of them worked.

  • Create new account
  • Reset your password

Hire Us!

Latest Releases

  • Tue, 06/09/2026 - 11:16
    gurux.dlms.java 4.0.95
  • Tue, 06/09/2026 - 10:03
    Gurux.DLMS.Python 1.0.199
  • Mon, 06/08/2026 - 13:39
    gurux.dlms.cpp 9.0.2606.0801
  • Mon, 06/01/2026 - 10:15
    gurux.dlms.cpp 9.0.2606.0101
  • Thu, 05/28/2026 - 16:06
    gurux.dlms.java 4.0.94

New forum topics

  • Error reading L&G Meter
  • Pass a TCP Client to GXNet
  • Australian EDMI Mk10D (Essential Energy area)
  • Strange mix of data notificiation vs get response
  • DLMS Connection
More

Who's new

  • Tuanhgg
  • Adel
  • charnon
  • Paddles
  • Miguel Ángel
RSS feed
Privacy FAQ GXDN Issues Contact
Follow Gurux on Twitter Follow Gurux on Linkedin