Hi,
I'm triying to read values of a Actaris SL7000, the comunication is ok. I create the device Manufacturer Actaris electricity, phisical server 11(17 decimal), logical server add 1, client id 10 (16 decimal). I got response of the metter but the only value I can read is 0.0.42.0.0.255 Logical Device Name and I want voltage, current, powers and energies values, but I can't add object to the list like.
I actually am trying to communicate with this same meter. The parameters selected are Client ID : 10 (hex)
Server ID : 1 (hex)
Wait time : 5
Authentication : None
Media : Serial
Manufacturer ID: ACE
Start Protocol : IEC.
I also checked the Use Logical Name Refrencing.
When I try to connect, I get a response "Failed to recieve reply from device in given time". I decided to monitor the serial line. I discovered that the Flag protocol actually is implemented but when the Gurux editor sends the SNRM Frame,the Meter does not reply, and I get that warning. Why is that so? And how can I fix it?
Actaris SL7000
Hi,
Your Authentication mode is None. Change it to Low and read again.
Actaris returns only name when authentication is not used.
BR,
Mikko
Actatris SL7000
I actually am trying to communicate with this same meter. The parameters selected are Client ID : 10 (hex)
Server ID : 1 (hex)
Wait time : 5
Authentication : None
Media : Serial
Manufacturer ID: ACE
Start Protocol : IEC.
I also checked the Use Logical Name Refrencing.
When I try to connect, I get a response "Failed to recieve reply from device in given time". I decided to monitor the serial line. I discovered that the Flag protocol actually is implemented but when the Gurux editor sends the SNRM Frame,the Meter does not reply, and I get that warning. Why is that so? And how can I fix it?
Thanks.
Actatris SL7000
Hi,
If meter is doing something important or that will take long time it will not answer. Then you have to wait for a while and try again.
You must use authentication to see more than plain meter name.
You can find default values here:
http://www.gurux.fi/GXDLMSDirectorExample
BR,
Mikko
Hi
Hi,
I have exactly this problem .. anyone solved the problem?
My meter only return COSEM logical device name...
Thanks, JP...
Actatris SL7000
Hi,
With low authentication SL7000 returns only name.
You must use low authentication.
See instructions here:
http://www.gurux.fi/GXDLMSDirectorExample
BR,
Mikko
Hi,
http://www.gurux.fi/GXDLMSDirectorExample
Actaris ACE SL7000
Hi,
I´m here to ask for a help about the SL7000 Smart meter.
The question is: How much (in percentage) is the deviation error caused if the phase sequence is not correct in a ACE SL7000 meter.
I'd be very grateful for your answer.
Regards,
A Santana
Actaris ACE SL7000
Hi,
I do not know if some one of community members can help with this but I can't.
Can you ask from Itron (Current owner of Actaris)?
BR,
Mikko