I thank you from my heart for your reply
I encountered problems during the ACE configuration SL7000
I need the following information
- HDLC Addressing Scheme _____________
- Physical Device ID ___________________
- Client ID __________________________
- Logical Device ID ____________________
- Application Context__________________
- Level Authentication (Password) ________
Good evening sir
Thank you for your assistance, the application works well I use it , but i need to knowl, but i need to know
Please can I ask you another question
it is possible to configure the sync 2000 for Ethernet TCP protocol ? if yes how ??
and another question please ??
is it possible to configure a sync gatway 2000 for Modbus RTU slave / mastre ??
Yes it is. Just change interface type from HDLC to WRAPPER. I can't remember client and server address now, but try to set 1 and 1. Let me know if that is not working.
I explain my problem, I am a student and I have a project to realize
I have 10 counters ACE SL7000 operation that the protocol DLMS / COSEM and I have a MicroLogix 1100 controllers supporting The Following communication protocols ethernet controller so I used a passrelle to change the protocol "SYNC 2000 '' that needs the EasyConnect Application
please, if you have informaion or a help from you
GXDLMSDirector it is also for configuring sync 2000?
how I can change in HDLC to WRAPPER
COMPTEUR INFORMATIONS
Hi,
You can read your SL7000 with GXDLMSDirector. You can get correct parameters from or here
http://www.gurux.fi/GXDLMSDirectorExample
BR,
Mikko
urgent !!!
Good evening sir
Thank you for your assistance, the application works well I use it , but i need to knowl, but i need to know
Please can I ask you another question
it is possible to configure the sync 2000 for Ethernet TCP protocol ? if yes how ??
and another question please ??
is it possible to configure a sync gatway 2000 for Modbus RTU slave / mastre ??
Ethernet TCP protocol
Hi,
Yes it is. Just change interface type from HDLC to WRAPPER. I can't remember client and server address now, but try to set 1 and 1. Let me know if that is not working.
BR,
Mikko
hi,
I explain my problem, I am a student and I have a project to realize
I have 10 counters ACE SL7000 operation that the protocol DLMS / COSEM and I have a MicroLogix 1100 controllers supporting The Following communication protocols ethernet controller so I used a passrelle to change the protocol "SYNC 2000 '' that needs the EasyConnect Application
please, if you have informaion or a help from you
GXDLMSDirector it is also for configuring sync 2000?
how I can change in HDLC to WRAPPER