Correct logic server for Landis & gyr CU modem

4 posts / 0 new
Last post
rheijser
Correct logic server for Landis & gyr CU modem

Hi,

I am trying to read out the parameters of a Landis & Gyr CU-P40 modem. According to Landis the correct logical address should be 17, but everytime I get the full parameters of the meter meter instead.

Kurumi
Kurumi's picture

Hi,

You need to change "Logical server address" for Landis + Gyr. This is L+G specific way to handle external connection parameters.

Open GXDLMSDirector and change "Logical server address" from zero to 1. Make a connection and read the association view again.

BR,
Mikko

________________________________________
Mikko Kurunsaari
Gurux Ltd
http://www.gurux.fi

rheijser

I have used logical server addres 1, see screenshot (P40). After collection objects the objects in screenshot P40_results are available. For example at register the objects U1, U2, U3, L1, L2 and L3 are shown which tells me the meter objects haven been collected.

Image: 
Kurumi
Kurumi's picture

Hi,

Your physical address is the serial number. Change it to 1. Change also the "Address Type" from SerialNumber to Default.

BR,
Mikko

________________________________________
Mikko Kurunsaari
Gurux Ltd
http://www.gurux.fi