I am trying to read out the parameters of a Landis & Gyr CU-P40 modem. According to Landis the correct logical address should be 17, but everytime I get the full parameters of the meter meter instead.
I have used logical server addres 1, see screenshot (P40). After collection objects the objects in screenshot P40_results are available. For example at register the objects U1, U2, U3, L1, L2 and L3 are shown which tells me the meter objects haven been collected.
Hi,
Hi,
You need to change "Logical server address" for Landis + Gyr. This is L+G specific way to handle external connection parameters.
Open GXDLMSDirector and change "Logical server address" from zero to 1. Make a connection and read the association view again.
BR,
Mikko
I have used logical server
I have used logical server addres 1, see screenshot (P40). After collection objects the objects in screenshot P40_results are available. For example at register the objects U1, U2, U3, L1, L2 and L3 are shown which tells me the meter objects haven been collected.
Hi,
Hi,
Your physical address is the serial number. Change it to 1. Change also the "Address Type" from SerialNumber to Default.
BR,
Mikko