GXDLMSDirector 9.0.2302.0901
Log created 11:10:43
11:10:57 Initializing serial connection.
11:10:58 IEC Sending:/?!<CR><LF>
11:11:00 HDLC received: /NIK5\2NIK2307 v2.00.<CR><LF>
System.Exception: Manufacturer type does not match. Manufacturer is NIK and it should be grx.
в GXDLMSDirector.GXDLMSCommunicator.InitSerial()
в GXDLMSDirector.GXDLMSCommunicator.InitializeConnection(Boolean force)
в GXDLMSDirector.GXDLMSDevice.InitializeConnection()
в GXDLMSDirector.MainForm.Connect(Object sender, GXAsyncWork work, Object[] parameters)
Can you please tell me where can I change the SNRM request length to 12 bytes?
Gurux send only 9 bytes.
In the native program, the request looks like this
7EA00A00000001219313D17E
Hi, Yes, you can add it by…
Hi,
Yes, you can add it by yourself. Read the instructions here:
https://www.gurux.fi/GXDLMSDirector.Manufacturers
If you send the device template to me, it can be added so it's available for all users.
BR,
Mikko
Thanks for the tip, if I…
Thanks for the tip, if I succeed, I'll be sure to share the result
Can you please tell me where…
Can you please tell me where can I change the SNRM request length to 12 bytes?
Gurux send only 9 bytes.
In the native program, the request looks like this
7EA00A00000001219313D17E
Can you add your own…
Can you add your own standard?
The native program seems to add a few bytes to the requests.