Hello, I have been trying to configure a TOU tariff on my meter trhough Gurux Director, however i have some doubts about how to implement a TOU structure in the meter.
I have create an Activity Calendar, then i have create an script table that contains all the OBIS code related with tariff 1:
1.0.1.8.1.255,1.0.1.8.2.255,1.0.1.8.3.255...
However in the configuration phase of this OBIS I dont really know what means the following parameters
Type:Execute or Write. What is the difference regarding this TOU for those parameters?What can I achieve with one or another?
Index: No idea
Parameter: No idea
Type:Uint16???
In the other hand, i dont know if i have to do something with the register activation. What does means the masks?
Thanks a lot for your help!
So the operation Type must be write or exectute?
However I don't really understand why do I have to select 4 in the index side. What does it means this value?
Hi,
Hi,
Script table script will write active_mask. You can try to change active_mask and you will see the correct parameters.
Index:4
Parameter: active_mask
Type:octet-string
BR,
Mikko
Thanks a lot for your help!
Thanks a lot for your help!
So the operation Type must be write or exectute?
However I don't really understand why do I have to select 4 in the index side. What does it means this value?
thanks in advanced
BR
Hi,
Hi,
#4 is the attribute index that you want to write.
BR,
Mikko