I'm testing our custom meter and facing an issue while reading special days table interface class.
By default there is no special days configuration meter, and when i'm reading special days table interface class, an error dialog box with "Data Bock Unavailable" message is displayed and gurux software gets disconnect from meter.
Is this general procedure for all meters, that meter will gets disconnected if there are no special days?
Can you help me with this issue ?
The request is correct and for some reason, the meter returns DataBlockUnavailable error.
Can you read anything else? I also notest that your client address is 0x64. I believe it should be 64.
Try if it helps.
Hi Anudeep,
Hi Anudeep,
Can you post the meter reply so I can verify it?
BR,
Mikko
Hello Mikko,
Hello Mikko,
Sorry for the delay. I have added meter response below.
16:42:52 Read object type SpecialDaysTable index: 2
TX: 7E A0 19 03 C9 BA 76 F7 E6 E6 00 C0 01 C1 00 0B 00 00 0B 00 00 FF 02 00 69 E5 7E
16:42:52
RX: 7E A0 11 C9 03 DA 92 3F E6 E7 00 C4 01 C1 01 0E 96 59 7E
16:42:53 Disconnect request
TX: 7E A0 07 03 C9 53 5A E0 7E
16:42:53
RX: 7E A0 1E C9 03 73 A0 B5 81 80 12 05 01 80 06 01 80 07 04 00 00 00 01 08 04 00 00 00 01 53 3B 7E
Thanks and Regards,
Anudeep Bhagwat
Hi,
Hi,
The request is correct and for some reason, the meter returns DataBlockUnavailable error.
Can you read anything else? I also notest that your client address is 0x64. I believe it should be 64.
Try if it helps.
BR,
Mikko