Skip to main content
Home
for DLMS smart meters
Open source solutions for DLMS smart metering

Main navigation

  • Home
  • Products
  • About us
  • Open Source
  • Community
  • Forum
  • Downloads
User account menu
  • Log in

Breadcrumb

  1. Home
  2. Forums
  3. Daisy Chaining Over IEC

Daisy chaining over IEC

Forum Rules

Before commenting read Forum rules

Don't comment the topic if you have a new question.

You can create a new topic selecting correct category from Gurux Forum and then create a new topic selecting "New Topic" from the top left.

By James_21 , 22 August, 2021
Forums
General discussion

is it possible to read energy meters through a transparent gateway over IEC protocol?
if yes , may i know the steps.

regards,
James

Profile picture for user Kurumi

Kurumi

4 years 9 months ago

Hi James,

Hi James,

You can read meters with daisy chain using DLMS, but not with IEC. IEC is a simple protocol and there is no meter information the frame that is needed to read values using daisy chain

BR,
Mikko

James_21

4 years 8 months ago

HI Kurumi,

HI Kurumi,

thank you for response.

is it possible to connect a single meter (not daisy chain) with transparent GW over RS485 interface with IEC protocol and perform time sync operation/or set desired time and date

regards,

Profile picture for user Kurumi

Kurumi

4 years 8 months ago

Hi,

Hi,

It should be possible. You can't change the baud rate during the initialization because GW usually can't handle it.

BR,
Mikko

James_21

4 years 8 months ago

i am surprised and thankful

i am surprised and thankful for swift responses.
baud rate during initialization; Does it mean starting baud rate 300 to default baud rate 9600?
Im sorry didnt get this... baud rate on Device as per IEC protocol must be;
300 or 9600..
Parity: Even or Odd
Data Bit: 7 or 8

regards
James

Profile picture for user Kurumi

Kurumi

4 years 8 months ago

Hi James,

Hi James,

It is a configurable parameter. :-)

When you communicate with an optical probe it's usually 300, but if you are operating with a serial port (RS-232 or RS-485), it can be anything. It's usually 9600.

Common optical probe default settings are: 300 7E1
Common serial port settings are 9600 8None1.

BR,
Mikko

James_21

4 years 8 months ago

Hi Kurumi,

Hi Kurumi,

May u share me ISKRA MT372 meter RS485 setting for IEC protocol,so i can test it with transparent GW.

regards,
James

Profile picture for user Kurumi

Kurumi

4 years 8 months ago

Hi James,

Hi James,

There are a lot of changes between IEC meters. You should check this. It's for Elster meters, but you can
try to read your meter in Mode A (readout mode) if you send "/?!\r\n"
https://www.gurux.fi/node/5415

BR,
Mikko

  • Create new account
  • Reset your password

Hire Us!

Latest Releases

  • Tue, 06/09/2026 - 11:16
    gurux.dlms.java 4.0.95
  • Tue, 06/09/2026 - 10:03
    Gurux.DLMS.Python 1.0.199
  • Mon, 06/08/2026 - 13:39
    gurux.dlms.cpp 9.0.2606.0801
  • Mon, 06/01/2026 - 10:15
    gurux.dlms.cpp 9.0.2606.0101
  • Thu, 05/28/2026 - 16:06
    gurux.dlms.java 4.0.94

New forum topics

  • Error reading L&G Meter
  • Pass a TCP Client to GXNet
  • Australian EDMI Mk10D (Essential Energy area)
  • Strange mix of data notificiation vs get response
  • DLMS Connection
More

Who's new

  • Tuanhgg
  • Adel
  • charnon
  • Paddles
  • Miguel Ángel
RSS feed