Hi,
I am facing below issue while writing Activity calendar- Passive day profile to the meter.

gurux.dlms.GXDLMSException: Access Error : Device reports a unmatched type.

----------CODE---------------------
GXDLMSActivityCalendar ac = new GXDLMSActivityCalendar(OBIS_ACTIVITY_CALENDAR);
com.readObject(ac, INDEX_PASSIVE_DAY_PROFILE_TABLE); //Reading index data
ac.setDayProfileTablePassive(new GXDLMSDayProfile[] {dp});
com.writeObject(ac, INDEX_PASSIVE_DAY_PROFILE_TABLE); // Writing Day Profile

----------TRACE DECRYPTED---------------------
Reading Passive Day Profile
TX: C0 01 C1 00 14 00 00 0D 00 00 FF 09 00
RX: C4 01 C1 00 01 01 02 02 11 01 01 03 02 03 09 04 02 00 00 00 09 06 00 00 0A 00 64 FF 12 00 01 02 03 09 04 0C 00 00 00 09 06 00 00 0A 00 64 FF 12 00 02 02 03 09 04 16 00 00 00 09 06 00 00 0A 00 64 FF 12 00 03
Writing Day Profile
TX: C1 01 C1 00 14 00 00 0D 00 00 FF 09 00 01 01 02 02 11 01 01 03 02 03 09 04 02 00 00 00 09 06 00 00 0A 00 64 FF 12 00 01 02 03 09 04 0C 00 00 00 09 06 00 00 0A 00 64 FF 12 00 02 02 03 09 04 16 00 00 00 09 06 00 00 0A 00 64 FF 12 00 03
RX: C5 01 C1 0C

Kindly do the needful...
Thanks & Regards
REMITH

Profile picture for user Kurumi

Kurumi

5 years 7 months ago

Hi,

Hi,

There is nothing that we can do about this. I checked the bytes and everything is correct.
This is a meter issue.

If you compare read and write trace you will notest that the payload is the same. I believe that you have read and try to write the same data. Ask the meter manufacturer to fix it.

BR,
Mikko

Remith

5 years 7 months ago

Thank you Mikko.. I will

Thank you Mikko.. I will contat the manufacturere team.

  • Create new account
  • Reset your password

Hire Us!

Latest Releases

  • Wed, 08/26/2026 - 09:04
    Gurux.DLMS.Python 1.0.203
  • Mon, 08/17/2026 - 11:28
    Gurux.DLMS.Python 1.0.202
  • Mon, 08/17/2026 - 09:47
    gurux.dlms.cpp 9.0.2608.1701
  • Mon, 08/17/2026 - 09:25
    gurux.dlms.c 9.0.2608.1701
  • Mon, 07/27/2026 - 12:37
    gurux.dlms.cpp 9.0.2607.2701

New forum topics

  • Security vulnerability report — request for a private contact (GuruxDLMS.c / ANSI C)
  • Topic: Insufficient Memory Error When Reading Class 7 Profile Generic Objects
  • SN ReadResponse returns all-null values when response spans multiple HDLC frames
  • Gurux.Serial.Android 3.0.6 – CH340 (HL-340) USB-Serial Adapter Not Working,
  • Trying to talk to a L&G E360 meter (Using Python Gurux)
More

Who's new

  • cyby
  • Metin Onan
  • ssv007
  • 3nzol3dur
  • dw772
RSS feed
Privacy FAQ GXDN Issues Contact
Follow Gurux on Twitter Follow Gurux on Linkedin