  2. Connection Problem To Iskra AM550

Connection problem to Iskra AM550

Forum Rules

Before commenting read Forum rules

Don't comment the topic if you have a new question.

You can create a new topic selecting correct category from Gurux Forum and then create a new topic selecting "New Topic" from the top left.

By Evgen , 30 July, 2021
Forums
DLMSDirector

Hello,
I have Iskra AM550-T (serial: 83 694 327) connected via serial port. I try to connect several times with different parameters but all time get errors like this

15:53:48 Initializing serial connection.
15:53:49 Send SNRM request.
7E A0 08 02 FF 03 93 92 5E 7E
15:53:54 Data send failed. Try to resend 1/3
15:53:59 Data send failed. Try to resend 2/3
15:54:04 Failed to receive reply from the device in given time.
15:54:04 Disconnect request
15:54:04 Send Disconnect request.
7E A0 08 02 FF 03 53 9E 98 7E
15:54:09 Data send failed. Try to resend 1/3
15:54:14 Data send failed. Try to resend 2/3
15:54:19 Failed to receive reply from the device in given time.

I think that something wrong with addresses.
One of setting see in attachment.
In one manual (for MT880) I found information " MT880 meters support single byte HDLC addressing. Default HDLC address set in the meter is calculated as follows: HDLC address = Last two digits from meter serial number + 10H " , but this don't work also.
Can anybody say right setting to connect to this device ?

Image
Profile picture for user Kurumi

Kurumi

4 years 10 months ago

Hi,

Hi,

MT880 settings might be different than AM550.

Try to change client address to from 64 to 1 and logical server to 0 and physical server address to 2B (Last two fight 27 + 16 = 27 = 0x2B).

BR,
Mikko

Evgen

4 years 10 months ago

Hi,

Hi,
got sane fail to receive reply from the device

GXDLMSDirector 8.2.2107.2101
Log created 10:16:40
10:17:29 Initializing serial connection.
10:17:30 Send SNRM request.
7E A0 07 57 03 93 0E F1 7E
10:17:35 Data send failed. Try to resend 1/2
10:17:40 Failed to receive reply from the device in given time.
10:17:40 Disconnect request
10:17:40 Send Disconnect request.
7E A0 07 57 03 53 02 37 7E
10:17:45 Data send failed. Try to resend 1/2
10:17:50 Failed to receive reply from the device in given time.
System.TimeoutException: Failed to receive reply from the device in given time.
в GXDLMSDirector.GXDLMSCommunicator.ReadDLMSPacket(Byte[] data, Int32 tryCount, GXReplyData reply)
в GXDLMSDirector.GXDLMSCommunicator.ReadDataBlock(Byte[] data, String text, Int32 multiplier, Int32 tryCount, GXReplyData reply)
в GXDLMSDirector.GXDLMSCommunicator.InitializeConnection(Boolean force)
в GXDLMSDirector.GXDLMSDevice.InitializeConnection()
в GXDLMSDirector.MainForm.Connect(Object sender, GXAsyncWork work, Object[] parameters)

Profile picture for user Kurumi

Kurumi

4 years 10 months ago

Hi,

Hi,

Do you have Low or High-level password for the meter? Or is this meter own by an electricity company?
If it's an electricity company meter, it might be that you can't connect to the meter and it is configured to send push messages. Are you receiving any data if you just listen to the serial port?

BR,
Mikko

Evgen

4 years 10 months ago

Hi,

Hi,
the problem was that default speed of rs-485 on meter is 115200 (but not 9600 I used).
Thanks for help, question cloused.

  • Create new account
  • Reset your password

Hire Us!

Latest Releases

  • Tue, 06/09/2026 - 11:16
    gurux.dlms.java 4.0.95
  • Tue, 06/09/2026 - 10:03
    Gurux.DLMS.Python 1.0.199
  • Mon, 06/08/2026 - 13:39
    gurux.dlms.cpp 9.0.2606.0801
  • Mon, 06/01/2026 - 10:15
    gurux.dlms.cpp 9.0.2606.0101
  • Thu, 05/28/2026 - 16:06
    gurux.dlms.java 4.0.94

New forum topics

  • Error reading L&G Meter
  • Pass a TCP Client to GXNet
  • Australian EDMI Mk10D (Essential Energy area)
  • Strange mix of data notificiation vs get response
  • DLMS Connection
More

Who's new

  • Tuanhgg
  • Adel
  • charnon
  • Paddles
  • Miguel Ángel
RSS feed
Privacy FAQ GXDN Issues Contact
Follow Gurux on Twitter Follow Gurux on Linkedin