Data what you are sending is correct. Can you check that IP address and port are correct.
You are accessing your meter directly. There is no Moxa, etc TCP/IP to serial port converter?
My device is a Transparent GPRS Modem, modem->meter connection is 485. I try connect to 9600,8,1,N and 9600,7,1,E connection setting. I success any other devices same config and gurux. for example ITRON SL7000, ISKRA 880 etc.
This device have CU. I see that CU must be parametrized as autonegotiation protocol.
When I set ICE initial protocol I also have no response from device.
When you are using L+G it uses IEC as starting protocol as default. Settings are 7E1.
Problem is if you want to use IEC as starting protocol settings are changed to 8E1 after moving to mode E.
Solution is force baud rate to 300 or set starting protocol to DLMS.
I did read Landys successfully with DLMS. But sometime (mostly) reply with error.
"Connection is permanently rejected. The application context name is not supported."
I restart meter then normally reading, but second try reply this error.
Landis Gyr E650 ZMD405CR
Hello,
Data what you are sending is correct. Can you check that IP address and port are correct.
You are accessing your meter directly. There is no Moxa, etc TCP/IP to serial port converter?
BR,
Mikko
My device is a Transparent
My device is a Transparent GPRS Modem, modem->meter connection is 485. I try connect to 9600,8,1,N and 9600,7,1,E connection setting. I success any other devices same config and gurux. for example ITRON SL7000, ISKRA 880 etc.
I try first time Landys.
:(
wait for your help. thanks.
CU
This device have CU. I see that CU must be parametrized as autonegotiation protocol.
When I set ICE initial protocol I also have no response from device.
Landis Gyr E650 ZMD405CR
Hi,
When you are using L+G it uses IEC as starting protocol as default. Settings are 7E1.
Problem is if you want to use IEC as starting protocol settings are changed to 8E1 after moving to mode E.
Solution is force baud rate to 300 or set starting protocol to DLMS.
BR,
Mikko
Success
Hi,
I did read Landys successfully with DLMS. But sometime (mostly) reply with error.
"Connection is permanently rejected. The application context name is not supported."
I restart meter then normally reading, but second try reply this error.
thanks
Landis Gyr E650 ZMD405CR
Hi,
Change "Use Logical Name Referencing" check box.
BR,
Mikko
Thanks
Thanks for all. :) I did it.