  2. Read Historical Data From Elster A1500

Read historical data from Elster A1500

Forum Rules

Before commenting read Forum rules

Don't comment the topic if you have a new question.

You can create a new topic selecting correct category from Gurux Forum and then create a new topic selecting "New Topic" from the top left.

Profile picture for user Fatih
By Fatih , 28 July, 2017
Forums
General discussion

I want to read historical data from Elster A1500
When I read data In Readout mode and with Optical Port meter is returning to me last 12 reset data like this

==> /?!<0D><0A>
<== /ABB5\@V4.50
==> <06>050<0D><0A>
Change Baud Rate:9600
<== -- STX --
F.F(00000000)
...
...
0.1.0(70) -- > Total Record
...
...
1.8.0(0001340.0*MWh)
1.8.0*70(0001139.2)
1.8.0*69(0000825.7)
... (12 Record)
1.8.0*59(0000000.0)
1.8.1(0000804.2*MWh)
1.8.1*70(0000643.8)
1.8.1*69(0000390.8)
... (12 Record)
1.8.1*59(0000000.0)
etc..

But when read with serial port in readout mode meter returns 1 historical data only.
F.F(00000000)
...
...
0.1.0(70) -- > Total Record
...
...
1.8.0(0001340.0*MWh)
1.8.0*70(0001139.2)
..
1.8.1(0000804.2*MWh)
1.8.1*70(0000643.8)
etc..

And When I Want read in programming mode meter returns wrong data

Standart Read
=> /?! CRLF
<= /ABB5\@V4.50
=> <ACK>051 CRLF
<= <SOH>P0<STX>(00391068)<ETX>e
Meter Ident:ABB Elster
=> <SOH>R5<STX>1.8.0()<ETX>^
<= <STX>1.8.0(0001340.0*MWh)<ETX>K

Last Reset Historical Data Read
=> <SOH>R5<STX>0.1.0()<ETX>V -> Total reset
<= <STX>0.1.0(70)<ETX>4 -> Reset Count 70
=> <SOH>R5<STX>0.1.2(70)<ETX>S -> Last Reset Date
<= <STX>0.1.2*70(0307171022)<ETX><US> -> 2017.07.03 17:10:22

=> <SOH>R5<STX>1.8.0(70) -> 70Th 1.8.0
<= <STX>1.8.0(0001340.0*MWh)<ETX>K -> !!!! This is wrong (Must be: 1.8.0*70(0001139.2) !!!!

And Here is a comedy too
=> SOH>R5<STX>0.1.2(69) -> Get then last 2nd data date (69)
<= <STX>0.1.2*70(0307171022)<ETX><US> !!! Whaaat?! !!! (70)

Where do I make mistakes.

Profile picture for user Kurumi

Kurumi

8 years 10 months ago

Read historical data from Elster A1500

Hi,

I'm sorry but I can't help you on this. I believe that is best if you ask this from meter vendor.
You are doing everything correctly, so I believe this is depends from the meter.

BR,

Mikko

  • Create new account
  • Reset your password

Hire Us!

Latest Releases

  • Tue, 06/09/2026 - 11:16
    gurux.dlms.java 4.0.95
  • Tue, 06/09/2026 - 10:03
    Gurux.DLMS.Python 1.0.199
  • Mon, 06/08/2026 - 13:39
    gurux.dlms.cpp 9.0.2606.0801
  • Mon, 06/01/2026 - 10:15
    gurux.dlms.cpp 9.0.2606.0101
  • Thu, 05/28/2026 - 16:06
    gurux.dlms.java 4.0.94

New forum topics

  • Error reading L&G Meter
  • Pass a TCP Client to GXNet