with GuruX DLMS Software - While connecting to Premier300 meter with Authentication - None (with ABCD0001 password given in manual - it is not connecting to meter) - we could find the default OBIS codes displayed with meterserialno - 0.0.96.1.0.255, clock - 0.0.1.0.0.255 which when read - displays the correct Meter Serial no and the clock - data and time. Similarly there is a OBIS code 0.0.96.1.0.255 which presumably contains energy values having the following structure when read in Data section - where in the hexadecimal values never change with time. Am i required to change Data type in Access Rights section - for Data Type and UIType - to get real-time data of energy values and what does Static mean - tick or untick. Or is there a different OBIS for energy values and how do i fetch them. Advise.
<Array>
<Structure>
<OctetString Value="01 00 01 08 00 FF" />
<UInt16 Value="221" />
</Structure>
<Structure>
<OctetString Value="01 00 05 08 00 FF" />
<UInt16 Value="217" />
</Structure>
<Structure>
<OctetString Value="01 00 08 08 00 FF" />
<UInt16 Value="218" />
</Structure>
<Structure>
<OctetString Value="01 00 09 08 00 FF" />
<UInt16 Value="216" />
</Structure>
<Structure>
<OctetString Value="01 00 94 08 00 FF" />
<UInt16 Value="212" />
</Structure>
<Structure>
<OctetString Value="01 00 8F 08 00 FF" />
<UInt16 Value="229" />
</Structure>
<Structure>
<OctetString Value="01 00 01 80 00 FF" />
<UInt16 Value="208" />
</Structure>
</Array>
Sorry - Energy OBIS Code is…
Sorry - Energy OBIS Code is 1.0.96.160.0.255
Hi, You don't use passwords…
Hi,
You don't use passwords with None authentication. You need to change the authentication level and client address as defined on the meter documentation.
Access Rights and available objects are updated when you connect with the correct authentication level. The meter decides the access rights and what objects are available with the selected authentication level and the client can't change them.
BR,
Mikko