  2. LANDIS E650 METER RS485 COMMUNICATION ISSUE

LANDIS E650 METER RS485 COMMUNICATION ISSUE

By Arunkumaran1 , 15 May, 2024
Forums
Gurux.DLMS

We urgently require your support for the subject case. Here are details. We have installed 4nos. of E650 meter equipped with E65 CU-XE communication modules in a 12kV VCB Panel where the RS485 connection doesnt establish with your DLMS test software. Please let me know what are points to be noted.

Profile picture for user Kurumi

Kurumi

2 years ago

Hi, At first, check your CU…

Hi,

At first, check your CU-XE settings. There are several settings with CU-XE that must be correct. Then check if you can read your meter with CU-XE client. In that way, you can verify that your connection can be established.

I believe that your server address is different from what is configured for the meter.

BR,
Mikko

  • Create new account
  • Reset your password

Hire Us!

Latest Releases

  • Tue, 06/09/2026 - 11:16
    gurux.dlms.java 4.0.95
  • Tue, 06/09/2026 - 10:03
    Gurux.DLMS.Python 1.0.199
  • Mon, 06/08/2026 - 13:39
    gurux.dlms.cpp 9.0.2606.0801
  • Mon, 06/01/2026 - 10:15
    gurux.dlms.cpp 9.0.2606.0101
  • Thu, 05/28/2026 - 16:06
    gurux.dlms.java 4.0.94

New forum topics

  • Error reading L&G Meter
  • Pass a TCP Client to GXNet
  • Australian EDMI Mk10D (Essential Energy area)
  • Strange mix of data notificiation vs get response
  • DLMS Connection
More
RSS feed
Privacy FAQ GXDN Issues Contact
Follow Gurux on Twitter Follow Gurux on Linkedin