Hi Mikko,
When I am trying to connect MR of a Iskra meter I am getting "ServiceError Initiate Error Exception. Initiate IncompatiableConformance" Exception. Below is the trace
Send AARQ request.
TX: 7E A0 68 03 41 10 D4 F9 E6 E6 00 60 5A A1 09 06 07 60 85 74 05 08 01 03 A6 0A 04 08 49 53 4B 30 30 30 30 31 8A 02 07 80 8B 07 60 85 74 05 08 02 01 AC 0A 80 08 49 53 4B 5F 53 45 43 31 BE 28 04 26 21 24 20 00 00 00 00 F4 8E 09 9D 35 20 46 1D 3E 2D 8B 8D 36 C7 1B 2A B7 4E E4 FB 9B 89 EF 6B A0 33 46 E8 E1 CA 14 61 2C 7E
RX: 7E A0 2D 41 03 30 2E 66 E6 E7 00 61 1F A1 09 06 07 60 85 74 05 08 01 03 A2 03 02 01 01 A3 05 A1 03 02 01 01 BE 06 04 04 0E 01 06 02 00 6D 7E
RX: 7E A0 20 41 03 73 3E 9D 81 80 14 05 02 02 00 06 02 02 00 07 04 00 00 00 01 08 04 00 00 00 01 6F EF 7E
Hi, Data is encrypted. I…
Hi,
Data is encrypted. I need block cipher and authentication keys.
BR,
Mikko
Hi Mikko, Here is the keys…
Hi Mikko,
Here is the keys
Block Cipher : 000102030405060708090A0B0C0D0E0F
AK : 000102030405060708090A0B0C0D0E0F
Hi, The meter returns an…
Hi,
The meter returns an Incompatible conformance error. One of your settings is different than the meter is expected. You need to ask correct settings from the meter vendor.
BR,
Mikko