By Bhaumik, 1 June, 2020 Forums General discussion Hi Mikko, I am testing the event from IS15959-2 meter. In that, I am able to receive and decode events. From the received event I can check set bit. From that, I can identify which type of event occurs but not able to identify which event occurs. e.g if bit no 84 set means "301/302-Meter load disconnected/Meter load connected" event received But is that actual event code is 301 or 302? How to identify that? Hi, Hi, You need to read Disconnect Control object 0.0.96.3.10.255 and check the state. State value is not save in IS 15959-2. Only status information that the state is changed is saved. BR, Mikko Log in or register to post comments
Hi, Hi, You need to read Disconnect Control object 0.0.96.3.10.255 and check the state. State value is not save in IS 15959-2. Only status information that the state is changed is saved. BR, Mikko
Hi,
Hi,
You need to read Disconnect Control object 0.0.96.3.10.255 and check the state. State value is not save in IS 15959-2. Only status information that the state is changed is saved.
BR,
Mikko